Abstract
This report details the work done to provide the U.S. Bureau of Mines with a customized Wireless Ground Monitor Wireless Ground Monitor was modified as follows: 1. A voltage regulator was added to prevent false trips with line voltage variations. 2. A Ground Wire Trap was designed to eliminate problems with parallel paths and provide spark suppression. 3. A three phase filter was designed to reduce 60 Hz leakage current. 4. A portable tester was designed to permit complete test of installed systems. 5. The design was modified to insure trip with an open ground wire in the event of a failure of any one semi-conductor component.