OFR-29-87 Sensitive Ground-Fault Protection For Mines - Phase II - Direct-Current Utilization

- Organization:
- The National Institute for Occupational Safety and Health (NIOSH)
- Pages:
- 81
- File Size:
- 23633 KB
- Publication Date:
- Jan 1, 1986
Abstract
The final report for Phase II of Bureau of Hines Contract J0134025 concerns the research and development of sensitive ground-fault relays for dc utilization systems in mining. Sensitive relaying employs very low pickup levels such that, when used in conjunction with very high resistance grounding, the exposure of a human to ventricular fibrillation is significantly reduced. To delineate the desired relay characteristics, the report begins by reviewing previous research in this area. A theory for the saturable transformer used to sense the fault current is presented. The design of the ground fault relay is described in sufficient detail that it may be duplicated. Test procedures and results are given. Finally, conclusions and recommendations related to Phase II are presented.