A portable calibrator to check tie trip setting of dc circuit breakers within an accuracy of +5% has been developed for the Bureau of Mines. It operates from a 300 volt dc trolley wire to provide controlled current pulses of 120 milliseconds duration and continuously adjustable from 1400 to 3600 A. These current pulses enable a breaker dc trip current to be determined and subject the contacts to full current rating. The equipment is simple to use and weighs 86 pounds. Connections are made with protected, clamp-on leads which are separately connected and weigh about 22 pounds. An accurate calibration procedure takes less than 5 minutes to complete.