RI 7515 Spatial And Temporal Distributions Of Halon 1301 From A Commercial Extinguisher

The National Institute for Occupational Safety and Health (NIOSH)
D. S. Burgess
Organization:
The National Institute for Occupational Safety and Health (NIOSH)
Pages:
20
File Size:
5108 KB
Publication Date:
Jan 1, 1971

Abstract

A commercially available Halon 1301 extinguisher has been evaluated as part of an explosion-suppression system for use in coal mines. Studies were made both of the dispersion pattern of the Halon 1301 at an initial pressure of 280 psig, and of the efficacy of this suppressant against 9.5 percent methane-air flames. These flames were quenched successfully only when the suppressant was applied before the fireball diameter exceeded 18 inches.
Citation

APA: D. S. Burgess  (1971)  RI 7515 Spatial And Temporal Distributions Of Halon 1301 From A Commercial Extinguisher

MLA: D. S. Burgess RI 7515 Spatial And Temporal Distributions Of Halon 1301 From A Commercial Extinguisher. The National Institute for Occupational Safety and Health (NIOSH), 1971.

Export
Purchase this Article for $25.00

Create a Guest account to purchase this file
- or -